- Product Details
- {{item.text}}
Quick Details
-
Brand Name:
-
GFUVE
-
Model Number:
-
GF4385
-
Accuracy:
-
0.5%
-
Power Supply:
-
Rechargeable lithium-ion battery 10000mAh
-
Input channels:
-
4 channel voltage, 4 channel current
-
Frequency:
-
40-70Hz
-
Phase shift:
-
0 - 1
-
Harmonic:
-
2 - 50 times
-
Voltage unbalance:
-
0.0%~ 100%
-
Three phases unbalance:
-
Yes
-
Energy parameters:
-
Wh, Varh, Vah.
-
Voltage flicker:
-
Yes
Quick Details
-
Warranty:
-
3 years
-
Power:
-
Electronic
-
Place of Origin:
-
Beijing, China
-
Brand Name:
-
GFUVE
-
Model Number:
-
GF4385
-
Accuracy:
-
0.5%
-
Power Supply:
-
Rechargeable lithium-ion battery 10000mAh
-
Input channels:
-
4 channel voltage, 4 channel current
-
Frequency:
-
40-70Hz
-
Phase shift:
-
0 - 1
-
Harmonic:
-
2 - 50 times
-
Voltage unbalance:
-
0.0%~ 100%
-
Three phases unbalance:
-
Yes
-
Energy parameters:
-
Wh, Varh, Vah.
-
Voltage flicker:
-
Yes
PORTABLE THREE PHASE POWER QUALITY ANALYZER
https://www.gfuvegroup.com/power-quality-analyzer/potable-three-phase-power-quality-analyzer.html
GF4385 portable power quality analyzer is a low cost PQA carefully developed by GFUVE GROUP and specially designed for field test of three phase system, multi-functional and intelligent, concise man-machine operation. It is easy to use, large LCD screen display, high resolution, English display, shock-proof shell structure and so on. simultaneously measure 4-channel current (I1 I2 I3 I4 three phase and neutral wire current) and 4-channel voltage (U1 U2 U3 U4 three-phase voltage and neutral line voltage to ground), the peak value of current voltage
Alarm function;
Snapshot function;
Transformer K factor;
Vector diagram display;
Inrush current monitoring;
Transient capture function;
Short-term voltage flicker (PST);
Total harmonic distortion (THD);
The DC components of voltages;
Peak current and voltage values;
Trend chart recording and storing function;
True RMS values of voltages and currents;
Three phase unbalance(current and voltage);
Measurement of each harmonic up to order 50;
Function | Analysis and diagnosis on all the voltage, current, power, energy, harmonic, each phase electric parameters etc. |
Accuracy | 0.5% |
Power Supply | Rechargeable lithium-ion battery 10000mAh. |
Input channels | 4 channel voltage, 4 channel current |
Rated voltage range(U1 U2 U3 U4 Un) | 0-1000V AC/DC (phase voltage) |
Rated voltage range(U1 U2 U3 U4) | 0-2000V AC/DC (line voltage) |
Rated current range(I1 I2 I3 I4) | 10A/100A/1000A/6000A |
Frequency | 40-70Hz |
Phase shift | 0 - 1 |
Harmonic | 2 - 50 times |
Total harmonic distortion | 2 - 50 times, each phase |
Voltage unbalance | 0.0%~ 100% |
Three phases unbalance | Yes |
Parameters of electricity | W, VA, Var, PF, DPF, cosφ, tanφ. |
Energy parameters | Wh, Varh, Vah. |
Number of Transient records | 150 sets |
Voltage flicker | Yes |
Record | 300 days(simultaneous recording 20 parameters, record one point every 5 seconds) |
Min/Max value | Yes |
LCD display | 5.6 inch color TFT LCD, 640×480, 4-bit LCD display, gray screen backlight |
Alarm Function | 40 different types of parameter selections, 12,800 sets alarm logs. |
Peak value | Yes |
Vector diagram display | Yes |
Snapshots | Yes, 60pcs |
Storage card | 2G |
Communication | USB Port |
Alarm Function | Yes |
Power Consumption | Current consumption of normal test 490 mA, continuous working for 10 hours. |
Insulation Resistance | ≥10MΩ (Between instrument wiring and shell) |
Withstand voltage | AC3kV/50Hz 1min (between instrument wiring and shell) |
Test cable | voltge cable 3m(5pcs), Crocodile clips(5pcs) |
PC software | Yes |
Standard | IEC61010-1, IEC61010-2-31, IEC60529(IP54), pollution grade 2, 1000V Cat III / 600V CAT IV, EN/IEC 61326; IEC 61000-4-30; IEC 61000-4-7, IEEE 519; IEC 61000-4-15; IEEE 1459; EN 50160 |