Quick Details
-
Working voltage range:
-
0.8~1.2Un
-
Frequency:
-
50/60Hz
-
Connection mode:
-
CT typeor direct type
-
Protection degree:
-
IP20
-
Accuracy class:
-
1.0
-
Constant:
-
6400imp
Quick Details
-
Phase:
-
Three Phase
-
Measuring Energy Range:
-
3*5A/CT
-
Place of Origin:
-
China
-
Working voltage range:
-
0.8~1.2Un
-
Frequency:
-
50/60Hz
-
Connection mode:
-
CT typeor direct type
-
Protection degree:
-
IP20
-
Accuracy class:
-
1.0
-
Constant:
-
6400imp
ELSINE 3X220/380V 50Hz LCD Three Phase Four Wire Prepaid Energy Meter Din-Rail Type RS485 Kwh Meter
Application
T he meter is used in three phase four wire /three phase three wire /two phase three wire power grid. The meter is designed to measure AC active energy. All of its functions comply with the relative technical requirement for class 1 three phase watt hour meter in IEC6 2053-21 . It is a long life meter with the advantage of high stability , high over load capability , low power loss and small volume .
Basic Function
1.LCD display 6+2
2.Bi-directional total active energy measurement ,reverse active energy measure in the total active energy
3.Pulse LED indicates working of meter , Pulse output with optical coupling isolation
4.loss phase LED indication , Reverse connection LED indication
5.RS485 communication port , MODBUS-RTU protocol
6.Energy data can store in memory chip more than 15 years after power off
7.35mm din rail installation
Technical Data
Rate voltage |
DTS238-7 RS485 three phase four wire 3x127/220V , 3x120/208V , 3x220/380V, 3x230/400V , 3x240/415V |
DSS238-7 RS485 three phase three wire(two phase three wire) 2x120/208V , 2x127/220 , 3x220V , 3x380V , 3x400V , |
|
Working voltage range |
0.8 ~ 1.2Un |
Rate Current |
5A/CT, 1.5(6)A,5(30)A ,5(60)A , 1 0(100)A, or other as required |
Frequency |
50Hz or 60Hz |
Connection mode |
CT type or Direct type |
Display |
LCD |
Accuracy class |
1.0 |
Power consumption |
< 0.5 W/ 5 VA /each phase |
Start current |
0.004Ib |
AC voltage withstand |
4000V/25mA for 60 sec |
Impulse Voltage |
6kV 1.2μs waveform |
IP grade |
IP20 |
Constant |
4 00 ~ 6400 imp/kWh |
Pulse output |
Passive pulse, pulse width is 80 + 5 ms |
Communication port |
RS485 port , baud rate 1200 ~ 96 00 bps , default is 96 00bps ,address 1 ~ 247,None parity , stop bits 1 , data bits 8 . |
Executive standard |
DIN 43880 IEC6 2053-21 IEC62052-11 |
Work temperature |
-30 ℃~ 70 ℃ |
Outline dimension LXMXH |
125x88x73mm |
Weight |
Approx 0. 7 kg |
Environment
Operating temperature |
- 25 ℃ ~ 55 ℃ |
Storage temperature |
- 4 0 ℃ ~ 8 0 ℃ |
Reference temperature |
23 ℃ + 2 ℃ |
Relative humidity |
0 to 95% , non-condensing |
Altitude |
U p to 2500m |
Warm up time |
10s |
Mechanical Environment |
M1 |
Electromagnetic Environment |
E2 |
Degree of pollution |
2 |
Wire connection
(1) three phase four wire direct connection
(2) three phase four wire through current transformer connection
(3) three phase three wire direct connection
(4) three phase three wire through current transformer connection
T erminal function