Silent hi-quality plastic wheel fan
built- in drein Pump and float switch
100% on line test
Specifications 2-pipe 4-way Cassett A series
|
|
|
|
|
|
|
|
|||||||
Model:M4KM*AP-A(E)
|
|
|
|
M4KM
200AP |
M4KM
300AP |
M4KM
400AP |
M4KM
450AP |
|||||||
CFM
|
|
|
|
240
|
300
|
450
|
500
|
|||||||
Air Flow Rate
|
|
High
|
m3/h
|
340
|
510
|
680
|
800
|
|||||||
|
|
Medium
|
m3/h
|
280
|
390
|
520
|
580
|
|||||||
|
|
Low
|
m3/h
|
180
|
260
|
350
|
390
|
|||||||
Cooling
|
Total Capacity
|
high
|
KW
|
2
|
2.3
|
4.2
|
4.5
|
|||||||
|
|
Medium
|
KW
|
1.8
|
2.3
|
3.1
|
3.8
|
|||||||
|
|
Low
|
KW
|
1.6
|
1.8
|
2.6
|
2.8
|
|||||||
|
Sensible Capacity
|
High
|
KW
|
1.5
|
1.9
|
2.6
|
2.9
|
|||||||
|
|
Medium
|
KW
|
1.3
|
1.7
|
2.6
|
2.9
|
|||||||
|
|
Low
|
KW
|
1.2
|
1.4
|
1.8
|
1.9
|
|||||||
|
Water Flow Rate
|
|
L/H
|
345
|
470
|
640
|
720
|
|||||||
|
Water Pressure Drop
|
|
kPa
|
7
|
9
|
11
|
14
|
|||||||
Heating
|
Heating Capacity
|
High
|
KW
|
2.8
|
4.2
|
5.6
|
6.3
|
|||||||
|
Heating Capacity
|
Medium
|
KW
|
2.5
|
3.4
|
4.5
|
5.5
|
|||||||
|
Heating Capacity
|
Low
|
KW
|
2
|
2.7
|
4
|
4.5
|
|||||||
Power Supply
|
|
|
|
220~240V/1PH/50Hz(or 60HZ)
|
|
|
|
|||||||
Power Input
|
|
|
W
|
39
|
52
|
60
|
68
|
|||||||
Sound Pressure
|
|
|
dB(A)
|
37
|
39
|
41
|
42
|
|||||||
Fan
|
Type
|
|
|
Centrifugal Fan
|
|
|
|
|||||||
|
Model
|
|
MM
|
315
|
315
|
315
|
315
|
|||||||
|
Quantity
|
|
|
1
|
|
|
|
|||||||
Motor
|
Type
|
|
|
3-speed Motor
|
|
|
|
|||||||
|
Quantity
|
|
|
1
|
|
|
|
|||||||
Coil
|
Coil Rows
|
|
|
2
|
|
|
|
|||||||
|
Max. Working Pressure
|
|
mPa
|
1.6
|
|
|
|
|||||||
|
Tube Diameter
|
|
Inch
|
3/8”
|
|
|
|
|||||||
Dimensions
|
Unit Body
|
|
MM
|
580x580x250
|
|
|
|
|||||||
|
Panel Assembly
|
|
MM
|
680x680x30
|
|
|
|
|||||||
Connection
|
Water Inlet/Outlet Pipe
|
|
Inch
|
ZG3/4”/ZG3/4”
|
|
|
|
|||||||
|
Condensate Discharge
|
|
Inch
|
26
|
|
|
|
|||||||
Weight(with feet, with casing)
|
|
|
KG
|
20
|
|
|
|
|||||||
1.Cooling: inlet air temp. DB+27oC/WB+19.5oC, water inlet/outlet temp. +7oC/+12oC
2.Heating: +21oC, water inlet temp. +60oC; Same water flow rate as for the cooling |
|
|
|
|
|
|
|