- Product Details
- {{item.text}}
Quick Details
-
Place of Origin:
-
Zhejiang, China
-
Brand Name:
-
JGGY
-
Model Number:
-
ZW32
-
Usage:
-
Electric Industry
-
OEM:
-
OEM Service
-
Warranty:
-
1 Year
-
Product name:
-
high voltage Vacuum circuit breaker indoor
-
Weight:
-
250KG
-
Rated voltage:
-
24kv
-
Rated current:
-
630A
-
Mechanical Life:
-
20000 Times
-
Packing:
-
1pc/box
-
Service:
-
OEM ODM Accept
Quick Details
-
Breaking Capacity:
-
25kA, 31.5kA
-
Rated Voltage:
-
12
-
Rated Current:
-
630
-
Place of Origin:
-
Zhejiang, China
-
Brand Name:
-
JGGY
-
Model Number:
-
ZW32
-
Usage:
-
Electric Industry
-
OEM:
-
OEM Service
-
Warranty:
-
1 Year
-
Product name:
-
high voltage Vacuum circuit breaker indoor
-
Weight:
-
250KG
-
Rated voltage:
-
24kv
-
Rated current:
-
630A
-
Mechanical Life:
-
20000 Times
-
Packing:
-
1pc/box
-
Service:
-
OEM ODM Accept
ZW32 series outdoor high voltage vacuum breaker is produced by Zhejiang Jingao High voltage electrical Co., Ltd., used in AC 50Hz ,rated voltage 12kV three-phase power system for closing/breaking load current,overcurrent and short-circuit current.the breaker can equip with reclosing controller to identiy break current characteristics and achieve multiple automatic reclosing or fault isolation.Self-provided PT as a power source,it becomes a smart circuit breake able to controlr with signal output of voltage and current.The electronic PT provides power supply and can complete three-stage composite protection of overcurrent delay, inrush current delay, and short-circuit and quick-break.
Ambient condition:
1. Ambient air temperature:Upper limit of +40℃,lower limit of -45℃;
2. Alititude: no more than altitude of 3000 meters(if need higher altitude its rated level accordingly).
3. Wind speed:no more than 34 m/s ;
4. Air pollution levels:no more than IV;
5. The surrounding air is not corrosive and flammable gas,steam and other significant pollution.
No. |
Description |
Unit |
Parameter |
||
1 |
Rated voltage |
kV |
12 |
24 |
|
2 |
Rated current |
A |
630 - 4000 |
630-3150 |
|
3 |
Rated frequency |
Hz |
50 |
50 |
|
4 |
Rated busbar current |
A |
630 - 4000 |
630-3150 |
|
5 |
Power frequency withstand voltage (1min) |
Phase to phase/earth |
kV |
42 |
65 |
Across the isolating distance |
48 |
79 |
|||
6 |
Lightning impulse withstand voltage |
Phase to phase/earth |
kV |
75 |
125 |
Across the isolating distance |
85 |
145 |
|||
7 |
Rated short circuit breaking current |
kA |
25, 31.5, 40 |
25, 31.5, 40 |
|
8 |
Rated short circuit making current (peak) |
kA |
63, 80, 100 |
63, 80, 100 |
|
9 |
Rated peak withstand current |
kA |
63, 80, 100 |
63, 80, 100 |
|
10 |
Rated short time withstand current |
kA |
25, 31.5, 40 |
25, 31.5, 40 |
|
11 |
During of short circuit |
s |
4 |
25, 31.5, 40 |
|
12 |
Protection degree |
|
Enclosure IP4X; partition between compartments IP2X |
Enclosure IP4X; partition between compartments IP2X |