Explore More Products
- Product Details
- {{item.text}}
Quick Details
-
Brand Name:
-
Shouke
-
Model Number:
-
100AF E-type
-
Rated current:
-
60a 75a 100a 125a
-
Product name:
-
MCCB
-
Rated voltage:
-
230/400V AC
-
Breaking capacity:
-
10kA
-
Application:
-
Power Control Panel
Quick Details
-
Breaking Capacity:
-
10kA
-
Rated Voltage:
-
380/440V
-
Place of Origin:
-
Zhejiang, China
-
Brand Name:
-
Shouke
-
Model Number:
-
100AF E-type
-
Rated current:
-
60a 75a 100a 125a
-
Product name:
-
MCCB
-
Rated voltage:
-
230/400V AC
-
Breaking capacity:
-
10kA
-
Application:
-
Power Control Panel
PRODUCT PARAMETERS
ABE data
Frame (AF) | 100 | ||
Breaking capacity (kA), Icu 415VAC | 10 | ||
Pole (P) | 2,3,4 | ||
Type | ABE102b | ||
ABE103b | |||
ABE104b | |||
Rated current ( A ) | 60,75,100 | ||
Technical parameter IEC/EN60947-2 | |||
Rated voltage (V), Ue (50/60Hz) | 600 | ||
Rated voltage (V), Ue (DC) | 250 | ||
Rated insulation voltage (V), Ui (50/60Hz) | 690 | ||
Rated pulse voltage (kV), Uimp | 6 | ||
Extreme short-circuit breaking capacity[Icu](kA) | AC 50/60Hz | 220V/240V | 25 |
380V | 14 | ||
415V | 10 | ||
440/460V | 10 | ||
480/500V | 7.5 | ||
600V | 5 | ||
DC | 125V | 10 | |
250V | 5 | ||
Service breaking capacity[Ics=%Icu] | 50 | ||
Endurance(Durability) | Mechanical | 8500 | |
Electrical | 1500 | ||
Accessory | |||
Internal | Auxiliary AUX | √ | |
Alarm switch ALT | √ | ||
Shunt trip SHT | √ | ||
Under voltage trip UVT | √ | ||
External | Rotary Handle | √ | |
Insulation terminal cover | √ | ||
Insulation barrier | √ | ||
Wiring behind the board | √ | ||
Installation and Dimensions | |||
Dimensions(mm)W*H*D | 75*130*60 | ||
Weight(kg) | 2/3/4P | 0.45/0.65/0.85 |
Hot Searches