- Product Details
- {{item.text}}
Quick Details
-
Model Number:
-
CE-XX
Quick Details
-
Network:
-
Modbus
-
Place of Origin:
-
Chongqing, China
-
Brand Name:
-
SSET
-
Model Number:
-
CE-XX
Product Description
This power transducer is a 1-phase AC voltage electrical isolation transducer.
DC voltage transducer 0-10V
using the principle of electromagnetic isolation, the input of the AC voltage and current signals are converted into standard analog signal output, to achieve the AC voltage signal measurement and monitoring.
The input and output of the
AC power transducer
have very good linearity. Moreover, the
AC current transducer 0-10V
is widely used in the following fields: telecommunications, electricity, railways, industrial monitoring and other fields.
Features
* Product voltage input port and power port have the strong anti-interference ability, and can withstand 4KV and 2KV surge impact;
* Safe and reliable: Input and output are isolated from each other;
* Easy to install: Rail or screw for installation.
* Safe and reliable: Input and output are isolated from each other;
* Easy to install: Rail or screw for installation.
Specification
item
|
value
|
Model Number
|
CE-VJ03-**MS*-0.5
|
Type
|
Current transducer
|
Place of Origin
|
Zhejiang
|
Brand Name
|
SSET
|
Usage
|
Industry, Railways, Electricity
|
Theory
|
The principle of electromagnetic isolation
|
Output
|
0-5V, 0-20mA, 0-10V, 4-20mA; 0-5KHz, 0-10KHz
|
Model
|
CE-VJ03-**MS*-0.5
|
Test condition
|
Room temperature: 25℃
|
Input range
|
Voltage 0-1V~500VAC
|
Output
|
0-5V, 0-20mA, 0-10V, 4-20mA;
0-5KHz, 0-10KHz |
Power supply
|
12V, 15V, 24V DC, 85-265V AC/DC (MS3 case)
|
Accuracy
|
0.5
|
Load capacity
|
≥2KΩ (voltage output);
≤250Ω (current output) |
Temperature drift
|
≤200ppm/°C
|
Isolation voltage
|
≥2500 VDC
|
Response time
|
≤300 mS
|
Rated power consumption
|
<0.5W
|
Output ripple
|
≤10mV
|
Frequency range
|
45~65Hz
(up to 5K, please specify when ordering) |
Surge immunity
|
Power port level: ± 0.5KV (L-N/2Ω/integrated wave)
Analog I / O port.± 0.5KV (L-N/40Ω/ integrated wave) |
Impulse immunity
|
Input / power port ± 2KV,
Analog I / O port ± 1KV |
Input overload capacity
|
Voltage: 2 times the nominal value
|
Operating temperature & Humidity
|
-10 ~ 60°C; ≤95 %( no dew)
|
Storage temperature & Humidity
|
-55 ~+65°C; ≤95 % (no dew)
|
Note: If you have any puzzles or requests about this product (including model number, data sheet or any other aspects), please contact us
immediately
.
Application
* Telecommunications
* Electricity
* Railways
* Industrial monitoring and other fields
* Electricity
* Railways
* Industrial monitoring and other fields
Certifications
Packing & Delivery
To better ensure the safety of your goods, professional, environmentally friendly, convenient and efficient packaging services will be provided.