PBM
centrifugal fans with backward curved aerodynamic impeller blades designed as freewheels fans that could be installed at any directions by extremely compact size, and optimized output air performance without scroll housing necessary to have.
- Product Details
- {{item.text}}
Quick Details
-
Place of Origin:
-
Jiangsu, China
-
Brand Name:
-
PBM
-
Model Number:
-
PB3N280B2EH
-
Voltage:
-
230VAC
-
Motor Type:
-
BE102AC
-
Usage:
-
Telecom Station, Heat Exchanger
-
Frame Material:
-
Aluminum Alloy
-
Rated Current:
-
1.58A
-
Air Pressure:
-
895PA
-
Certificate:
-
LVD En 60950-1
-
EMC En 61000-6-3:
-
En 61000-4-2 and En 61000-4-3
-
Certification:
-
CE RoHS ErP
-
Life Span:
-
50,000Hours
-
Protection Type:
-
IP44
Quick Details
-
Applicable Industries:
-
Garment Shops, Building Material Shops, Machinery Repair Shops, Food & Beverage Factory, Restaurant
-
Electric Current Type:
-
AC
-
After-sales Service Provided:
-
Online support
-
Place of Origin:
-
Jiangsu, China
-
Brand Name:
-
PBM
-
Model Number:
-
PB3N280B2EH
-
Voltage:
-
230VAC
-
Motor Type:
-
BE102AC
-
Usage:
-
Telecom Station, Heat Exchanger
-
Frame Material:
-
Aluminum Alloy
-
Rated Current:
-
1.58A
-
Air Pressure:
-
895PA
-
Certificate:
-
LVD En 60950-1
-
EMC En 61000-6-3:
-
En 61000-4-2 and En 61000-4-3
-
Certification:
-
CE RoHS ErP
-
Life Span:
-
50,000Hours
-
Protection Type:
-
IP44
Products Description
Higher Air Performance with Less Power Consumption
Product Specification
1. General Characters
Model
|
PB3N280B2EH
|
Rated Voltage
|
230 VAC
|
Operating Voltage
|
184~277 VAC
|
Rated Speed
|
2750 RPM
|
Input Current
|
1.75 A
|
Input Power
|
390 W
|
Air Flow
|
1649CFM /2800m3/H
|
Static Pressure
|
3.58inH2O / 895Pa
|
Sound Level
|
80 dB(A)
|
Protection Type
|
IP44
|
2.
Mechanical
Dimension
|
Ø281mm X 173mm (see dimension drawing)
|
Material of Impeller
|
Galvanized metal Sheet
|
Number of Blades
|
11
|
Mounting Position
|
Any
|
Surface of Rotor
|
Coated in black
|
Bearing System
|
NMB ball bearing
|
Lead Wire
|
AC(AWG20#),DC(AWG22 #)
|
Weight
|
5000g
|
Package
|
Standard
|
3.
Electrical Protection
Locked-rotor Protection
|
Over-current limiting circuit protects motor from damage at least for 72 hours of locked rotor condition at rated voltage.
|
under Locked Rotor |
A, Typical inrush current when the motor is trying to re-start under locked rotor conditions is 2~4 times the normal running
current reoccurring and for 16~20% of restarting cycle period. B, If he CL function is used this restarting inrush current is about the same as the normal running current. |
Reverse Polarity Protection
|
No damage if the positive and negative leads are reversed under maximum operation voltage conditions.
|
Over Voltage Protection
|
The circuit will be shut down automaticlly when input voltage over threshold. And re-started when Voltage down to threshold below.
|
Soft Start
|
In 5 seconds after power on and speed control voltage gets to 1.5V or PWM duty cycle at 10% above.
|
4. Outline Drawing