- Product Details
- {{item.text}}
Quick Details
-
Place of Origin:
-
Zhejiang, China
-
Brand Name:
-
GP, Greenpower
-
Model Number:
-
GPR2-12(D)/T630-20-I
-
Material:
-
Stainless steel/Alu-zinc steel, Stainless steel, Alu-zinc sheet
-
BIL:
-
65kV/125kV
-
Rated frequency:
-
50Hz, 60Hz
-
Degree of Protection:
-
Gas Tank IP67, Enclosure IP4X
-
Mechanical life:
-
5000 times
-
Operation sequence:
-
O-0.3s-CO-180s-CO
-
Color:
-
RAL7032, RAL7035
-
Website:
-
www.sinogp.com
Quick Details
-
Voltage:
-
12000, 11000, 10000
-
Current:
-
630
-
Size:
-
350
-
Place of Origin:
-
Zhejiang, China
-
Brand Name:
-
GP, Greenpower
-
Model Number:
-
GPR2-12(D)/T630-20-I
-
Material:
-
Stainless steel/Alu-zinc steel, Stainless steel, Alu-zinc sheet
-
BIL:
-
65kV/125kV
-
Rated frequency:
-
50Hz, 60Hz
-
Degree of Protection:
-
Gas Tank IP67, Enclosure IP4X
-
Mechanical life:
-
5000 times
-
Operation sequence:
-
O-0.3s-CO-180s-CO
-
Color:
-
RAL7032, RAL7035
-
Website:
-
www.sinogp.com
Product show
12kV 24kV SF6
Gas Insulated Ring Main Unit
Switchgear
Technology & details
Description
|
|
Unit
|
LBS unit
|
Switch-fuse Unit
|
VCB
|
Busbar subsection unit
|
||||
|
|
|
|
|
Unit
|
|
||||
Rated voltage
|
|
kV
|
12
|
12
|
12
|
12
|
||||
|
Phase to phase/earth
|
kV
|
42
|
42
|
42
|
42
|
||||
|
Across the isolating distance
|
kV
|
48
|
48
|
48
|
48
|
||||
|
Phase to phase/earth
|
kV
|
75, (95)*
|
75, (95)*
|
75, (95)*
|
75, (95)*
|
||||
|
Across the isolating distance
|
kV
|
85, (110)*
|
85, (110)*
|
85, (110)*
|
85, (110)*
|
||||
Rated frequency
|
|
Hz
|
50,60
|
50,60
|
50,60
|
50,60
|
||||
Rated current
|
|
A
|
630
|
①
|
630
|
630
|
||||
Rated short circuit breaking current
|
|
kA
|
|
②
|
20,(25)*
|
|
||||
Rated short time withstand current
|
|
kA/s
|
20/3
(20/4, 25/1)*
|
|
20/3
(20/4, 25/3)*
|
20/3
(20/4, 25/1)*
|
||||
|
|
|
|
|
|
20/3, (20/4, 25/1)*
|
||||
Rated peak withstand current
|
|
kA
|
50, (63)*
|
|
50, (63)*
|
50, (63)*
|
||||
Rated short circuit making current
|
|
kA
|
50, (63)*
|
②
|
50, (63)*
|
50, (63)*
|
||||
Rated transfer current
|
|
A
|
|
1800
|
|
|
||||
Rated active load breaking current
|
|
A
|
630
|
|
|
630
|
||||
Rated closed loop breaking current
|
|
A
|
630
|
|
|
630
|
||||
5% rated active load breaking current
|
|
A
|
31.5
|
|
|
31.5
|
||||
Rated operating sequence
|
|
|
|
|
O-0.3s-CO-180s-CO
|
|
||||
Mechanical lifetime
|
|
Ops
|
5000
|
5000
|
10000
|
5000
|
||||
Electrical lifetime
|
|
|
E3
|
|
E2
|
E3
|
||||
Thickness of stainless steel
|
|
mm
|
3
|
|
|
|
||||
Rated SF6 pressure
|
|
kPa
|
30 (at 20℃ , 101.3kPa)
|
|
|
|
||||
Annual leakage rate
|
|
|
<0.02%
|
|
|
|
||||
Water treatment test
|
|
|
12kV 24 hours (at 30 kPa under the water)
|
|
|
|
||||
Internal arc test
|
|
|
20kA 1s
|
|
|
|
||||
|
Gas tank
|
|
IP67
|
|
|
|
||||
Protection degree
|
Fuse holder
|
|
IP67
|
|
|
|
||||
|
GPR enclosure
|
|
IP4X
|
|
|
|
Strict quality control system
* Strict partial discharge testing and control of the whole machine and components
* Background of partial discharge testing room: ≤0.5pC
* Partial discharge of the whole equipment under 1.1Un ≤10pC
Ensure the insulation reliability of the equipment under long-term operation!
* Strict partial discharge testing and control of the whole machine and components
* Background of partial discharge testing room: ≤0.5pC
* Partial discharge of the whole equipment under 1.1Un ≤10pC
Ensure the insulation reliability of the equipment under long-term operation!